- Out-of-Stock
The Evikon E2218-DM duct humidity and temperature transmitter measures air conditions inside ventilation ducts and provides calculated dew point and absolute humidity values.
Connect duct humidity and temperature measurements to your HVAC controller or building management system with the Evikon E2218-DM. Its 200 mm probe positions the sensor inside the ventilation duct, while analog outputs and RS485 Modbus RTU provide connection options for compatible control and monitoring equipment.
The transmitter measures relative humidity and temperature in air and non-aggressive gases. Dew point and absolute humidity are calculated from these measurements.

The E2218-DM provides two configurable analog outputs, each selectable as 4–20 mA or 0–10 V, with adjustable scales. The RS485 Modbus RTU interface supports digital communication with a compatible host system.
For a new installation, specify the signals accepted by your controller and the required measurement scales. When replacing a transmitter, check the existing wiring, supply voltage and input configuration before selecting the replacement.
| Connection option | What to confirm |
|---|---|
| 4–20 mA | Controller input compatibility, wiring arrangement and configured measurement scale. |
| 0–10 V | Voltage-input compatibility, signal reference and configured measurement scale. |
| RS485 Modbus RTU | Host support, communication settings and the registers required for your application. |
| Parameter | Specification |
|---|---|
| Model | E2218-DM |
| Humidity range | 0–100% RH, non-condensing |
| Temperature range | -40 to +85°C |
| Calculated parameters | Dew point and absolute humidity |
| Standard accuracy | ±2.5% RH / ±0.3°C |
| Optional accuracy | ±1.8% RH / ±0.3°C, on request |
| Resolution | 0.01% RH / 0.01°C |
| Power supply | 12–36 VDC standard; 24 VAC option |
| Enclosure protection | IP65 |
| Probe dimensions | Ø16 × 200 mm |
Select a measurement position that represents the air conditions you need to control. Check the available insertion space, access for servicing and the routing of power and signal cables.
For installations near humidifiers, cooling coils or other sources of moisture, assess the possibility of condensation at the sensing point. The specified operating conditions are non-condensing.

A clear specification helps match the transmitter to the control system without unnecessary changes during installation. Include:
Contact us for pricing and availability. Include the quantity, power-supply option and required outputs. For a replacement enquiry, send the existing transmitter model number and controller input details.